REFLECTIVE BEAM SMOKE DETECTOR FIRERAY 50RU/100RU

  • Tổng Quát
  • Tài Liệu
  • Hỗ Trợ
Chuyên Mục: Detectors

 Description

  • The system comprises of a single unit incorporating an infra-red transmitter and receiver.The signal gen erated in the transmitter element and reflected by the prism back to the receiver element is analyzed for the presence of smoke.The internal microprocessor determines an alarm condition when a predetermined level is reached.
  • The system is designed to be mounted so the beam will project between 19” (0.5 m) and 24” (0.6m) be low and parallel to the ceiling. Lateral detection may be up to 30ft. (9.144m) on either side of the beam, providing a maximum total coverage area of up to 19,800 square feet (60ft. x 330ft. or 18.29m x 100m)
Features
  •  2 Models for ranges of:50RU: 16.5 ft. to 160 ft. (5m to 50m); 100RU: 160 ft. to 330 ft. (50m to 100m)
  •  Easy set up and alignment
  •  Single compact housing
  • Calibrated obscuration test flter included
  •  3 selectable alarm thresholds: 25%, 35% or 50%
  •  Microprocessor controlled
  •  Alarm latching or auto reset
  •  Automatic gain control
  •  12 VDC or 24 VDC operation
  •  Separate alarm and trouble contacts
  •  Remote Test Station available
  •  3YearWarranty