The system comprises of a single unit incorporating
an infra-red transmitter and receiver.The signal gen
erated in the transmitter element and reflected by the
prism back to the receiver element is analyzed for
the presence of smoke.The internal microprocessor
determines an alarm condition when a predetermined
level is reached.
The system is designed to be mounted so the beam
will project between 19” (0.5 m) and 24” (0.6m) be
low and parallel to the ceiling. Lateral detection may
be up to 30ft. (9.144m) on either side of the beam,
providing a maximum total coverage area of up to
19,800 square feet (60ft. x 330ft. or 18.29m x 100m)
Features
2 Models for ranges of:50RU: 16.5 ft. to 160 ft. (5m to 50m); 100RU: 160 ft. to 330 ft. (50m to 100m)